Overview
|
|
DataSheet
|
|
Active Ethernet I/O with 4 analog inputs and 12 configurable DIO
Better I/O matrix for monitoring
Moxa's ioLogik
E2242 is tailor made for use with remote monitoring and alarm systems.
This Active Ethernet I/O product provides 4 analog inputs and 12
configurable DIOs in the same product. The 1:3 ratio of analog to
digital IOs is perfectly adapted for water tank monitoring and
environmental monitoring applications, in which 1 analog input is used
to trigger 3 digital outputs as High-High, High, and Low alarms. Moxa's
ioLogik E2242 lets you set up your monitoring system without the need
for a local PC or RTU.
Features and Benefits
- 4 fixed differential analog input
channels
- 12 configurable digital input/output
channels
- Instant event messaging by TCP, UDP,
e-mail, SNMP Trap
- PC-based configuration utility and
web console
- Easy-to-use Click&Go™ Logic for
local output control
- I/O control over Modbus/TCP and SNMP
protocol
- NIST traceable calibration
Specifications
|
LAN: |
| Ethernet |
10/100Mbps, RJ45 |
| Protection |
1.5KV magnetic
isolation |
| Protocols |
Modbus/TCP,
TCP/IP, UDP, DHCP, Bootp, SNMP(MIB for I/O and Network), HTTP, SNTP |
|
Serial: |
| Interface |
RS-485-2w: Data+,
Data-, GND |
| Serial
Line Protection |
15KV ESD for all
signals |
|
Serial Communication Parameters: |
| Data
Bits |
8 |
| Stop
Bits |
1 |
| Parity |
None |
| Flow
Control |
None |
| Protocols |
Modbus/RTU |
| Speed |
1200 to 115200 bps |
|
Digital Input: |
| Sensor
Type |
NPN, PNP |
| I/O
Mode |
DI or event
counter (up to 900 Hz) |
| Dry
Contact |
Logic 0: short to
GND
Logic 0: Open |
| Wet
Contact |
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC |
| Common
Type |
6 points per COM |
| Power
Off Storage for Counter Mode |
Yes |
|
Digital Output: |
| Sensor
Type |
Sink, 36 VDC, 200
mA |
| Pulse
Wave Width |
10 ms /100 Hz |
|
Configurable Digital
Input/Output Channels: |
| Channels |
12 points |
|
Analog Input: |
| Resolution |
16-bit |
| Accuracy |
±0.1% FSR @
25?C, ±0.3% FSR @ -10 and 60?C |
| Sampling
Rate (all channels) |
100 samples/sec |
| Input
Impedence |
200K ohms (min.) |
| Built-in
Resistor for Current Input |
102 ohms |
| Channels |
4, differential
input |
|
Physical Characteristics: |
| Wiring |
I/O cable max.
14AWG |
|
Environmental Limits: |
| Operating
Temperature |
-10 to 60°C
(14 to 140°F) |
| Storage
Temperature |
-40 to 85°C
(-40 to 185°F) |
| Ambient
Relative Humidity |
5 to 95%
(non-condensing) |
|
Power Requirements: |
| Power
Input |
24 VDC nominal, 12
to 48 VDC |
| DO
Power |
24 VDC nominal, up
to 30 VDC |
|
Agency Approvals: |
| EMI |
FCC Part 15, CISPR
(EN55022) class A |
| EMS |
IEC 61000-4, IEC
61000-6 |
| Safety |
UL508 |
| Shock |
IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Vibration |
IEC 60068-2-6 |
Specification
| Power Requirements |
| Power Consumption |
178 mA @ 24 VDC |
| Power Input |
24 VDC nominal, 12 to 36 VDC |
| Serial Communication Parameters |
| Flow Control |
None |
| Protocol |
Modbus/RTU |
| Data Bits |
8 |
| Parity |
None |
| Stop Bits |
1 |
| Baudrate |
1200 to 115200 bps |
| Analog Input |
| Type |
Differential input |
| Input Impedance |
200K ohms (min.) |
| Built-in Resistor for Current Input |
120 ohms |
| Resolution |
16 bits |
| Input Range |
±150 mV, 0 to 150 mV, ±500 V, 0 to 500 mV, ±5 V, 0 to 5 V, ±10 V, 0 to 10 V, 0 to 20 mA, 4 to 20 mA |
| Sampling Rate (all channels) |
100 samples/sec |
| Accuracy |
±0.1% FSR @ 25°C ±0.3% FSR @ -10 and 60°C |
| I/O Mode |
Voltage / Current |
| Inputs and Outputs |
| Analog Inputs |
4 channels |
| Configurable DIOs |
12 channels |
| LAN |
| Protection |
1.5 KV magnetic isolation |
| Ethernet |
1 x 10/100 Mbps, RJ45 |
| Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, HTTP, CGI, SNTP |
| Digital Input |
| Isolation |
3K VDC or 2K Vrms |
| Poweroff Counter |
Supports poweroff counter storage function |
| Common Type |
6 points per COM |
| Over-voltage Protection |
36 VDC |
| Digital Filtering Time Interval |
Software selectable |
| Dry Contact |
• On: short to GND • Off: Open |
| Wet Contact |
• On: 0 to 3 VDC • Off: 10 to 30 VDC |
| Counter Frequency |
900 Hz, power off storage |
| I/O Mode |
DI or event counter |
| Sensor Type |
Wet Contact (NPN or PNP) and Dry Contact |
| Environmental Limits |
| Operating Temperature |
-10 to 60°C (14 to 140°F) |
| Storage Temperature |
-40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity |
5 to 95% (non-condensing) |
| Physical Characteristics |
| Weight |
under 250 g |
| Dimensions |
115 x 79 x 45.6 mm (4.53 x 3.11 x 1.80 in) |
| Wiring |
I/O cable max. 14 AWG |
| Standards and Certifications |
| EMI |
FCC Part 15 Subpart B Class A, EN 55022 Class A |
| Safety |
UL 508 |
| Shock |
IEC 60068-2-27 |
| Vibration |
IEC 60068-2-6 |
| EMS |
IEC 61000-4, IEC 61000-6 |
| Freefall |
IEC 60068-2-32 |
| Digital Output |
| Type |
Sink |
| Isolation |
2K Vrms or 3K VDC (Magnetic) |
| Pulse Output Frequency |
1 kHz |
| Over-temperature Shutdown |
175°C (min.) |
| Over-voltage Protection |
45 VDC |
| Current Rating |
200 mA per channel |
| I/O Mode |
DO or Pulse Output |
| Over-current Protection |
2.6 A (4 channels @ 650 mA) |
| Serial Communication |
| Interface |
RS-485-2w: Data+, Data-, GND |
| Serial Line Protection |
15 KV ESD for all signals |
| MTBF (mean time between failure) |
| Time |
204,391 hrs |
| Database |
Telcordia (Bellcore) |
| Warranty |
| Warranty Period |
5 years |
| Details |
See www.moxa.com/warranty |
|
|
Project Evaluation Request
Tel: 1-877-235-6628
Fax: 1-866-640-5851
Product Overview
DataSheet
MOXA