Overview
|
|
DataSheet
|
|
The ioLogik W5340 is designed for cellular remote monitoring and alarm
systems, such as automated river monitoring and pipeline monitoring.
The ioLogik W5000 series uses GPRS technology to maximize the coverage
of remote monitoring applications. This kind of application needs
cellular communications and I/O points connected to various sensors,
including rainfall meters, flow meters, and water level detectors,
since installing devices is usually difficult. They all enjoy the
benefit of the GPRS communication feature of ioLogik W5340.
- GPRS, Ethernet LAN, RS-232/422/485
supported
- Smart Active GPRS connection
- Low power consumption
- Secure wake on call ID
- Active messaging with real-time
stamp
- Data logging with SD card
- Unicode Active Messaging with
real-time stamp, including SMS, SNMP Trap with I/O status, TCP, email
- ioAdmin and Active OPC Server
supported
- Windows/WinCE VB/VC.NET and Linux C
APIs
| Cellular Interface |
| Interface |
GPRS |
| Band
Options |
Quad-band
850/900/1800/1900 MHz |
| GPRS
Multi-Slot Class |
Class 10 |
| GPRS
Terminal Device Class |
Class B |
| SMS |
Point-to-Point
Text/PDU |
| SIM
Interface |
3 V |
| Serial
Communication |
| Interface |
1 x
RS-232/422/485, software selectable
(9-pin D-Sub, male or 5-contact terminal block) |
| Baudrate |
1200, 2400, 4800,
9600, 19200, 38400, 57600, 115200 bps |
| LAN: |
| Ethernet |
1 x 10/100 Mbps,
RJ45 |
| Protection |
1.5 KV magnetic
isolation |
| Protocols |
Modbus/TCP,
TCP/IP, UDP, DHCP, Bootp, SNMP, SNTP |
| Analog
Input: |
| Channels |
4 analog inputs
with differential input |
| Resolution |
16 bits |
| I/O
Mode |
Voltage / Current |
| Input
Range |
0 to 10 V,
±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA |
| Accuracy |
±0.1% FSR @
25°C
±0.3% FSR @ -10 and 55°C |
| Sampling
Rate (all channels) |
100 samples/sec |
| Input
Impedence |
200K ohms (min.) |
| Built-in
Resistor for Current Input |
102 ohms |
| DI/DO
Configurable Channels: |
| Channels |
8 |
| I/O
Mode |
DI or Event
Counter (up to 900 Hz)
DO or Pulse Output (up to 100 Hz) |
| Digital
Input: |
| Channels |
Up to 8,
source/sink selectable |
| Sensor
Type |
NPN/PNP type |
| I/O
Mode |
DI or Event
Counter (up to 900 Hz) |
| Dry
Contact |
Logic 0: short to
GND
Logic 1: open |
| Wet
Contact |
(For Source Type)
Logic 0: 0 to 3 VDC
Logic 1: 10 to 30 VDC (DI COM to DI) |
| Common
Type |
4 points per COM |
| Isolation |
3K VDC or 2K Vrms |
| Counter/Frequency |
900 Hz, power off
storage |
| Digital
Filtering Time Interval |
Software selectable |
| Over-voltage
Protection |
36 VDC |
| Poweroff
Counter Memory |
48 bytes |
| Digital
Output: |
| Channels |
Up to 8, sink
type, 36 VDC, 200 mA |
| I/O
Mode |
DO or Pulse Output
(up to 100 Hz) |
| Pulse
Wave Width/Frequency |
10 ms/100 Hz |
| Over-voltage
Protection |
45 VDC |
| Over-current
Limit |
600 mA |
| Over-temperature
Shutdown |
160°C |
| Output
Current Rating |
Max. 200 mA per
channel |
| Isolation |
3K VDC or 2K Vrms |
| Relay
Output |
| Channels |
2 Form A (N.O.)
relay outputs, 5 A |
| Contact
Rating |
5 A @ 30 VDC, 5 A
@ 240 VAC, 5 A @ 110 VAC |
| Inductance
Load |
2 A |
| Resistance
Load |
5 A |
| Breakdown
Voltage |
500 VAC |
| Relay
On/Off Time |
10 ms, 5 ms (max.) |
| Initial
Insulation Resistance |
1G min. @ 500 VDC |
| Expected
Life |
100,000 times
(Typical) |
| Initial
Contact Resistance |
30 milli-ohms
(max.) |
| Pulse
Output |
20 operation times
per minutes at rated load |
| Isolation |
3K VDC or 2K Vrms |
| Physical
Characteristics |
| Dimensions |
46.8 x 135 x 105
mm (1.84 x 5.31 x 4.13 in) |
| Power
Requirements |
| Power
Consumption |
GPRS Always On
(Communication): 4.2 W
GPRS Off: 2.8 W |
| Power
Input |
24 VDC nominal, 12
to 36 VDC |
| Environmental
Limits |
| Operating
Temperature |
-10 to 55°C
(14 to 131°F) |
| Storage
Temperature |
-40 to 85°C
(-40 to 185°F) |
| Ambient
Relative Humidity |
5 to 95%
(non-condensing) |
| Regulatory
Approvals |
| Safety |
UL 508 (Pending) |
| EMI |
FCC part 15, CISPR
(EN55022) Class A |
| EMS |
IEC 61000-4-2
(ESD), level 2/3
IEC 61000-4-3 (RS), level 2
IEC 61000-4-4 (EFT), level 2
IEC 61000-4-5 (Surge), level 3
IEC 61000-4-6 (CS), level 2
IEC 61000-4-8 (PM), level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2 (ESD), level 2/3
IEC 61000-6-4 (EFT), level 2 |
| Shock |
IEC 60068-2-27 |
| Freefall |
IEC 60068-2-32 |
| Vibration |
IEC 60068-2-6 |
| Warranty |
| Warranty
Period |
2 years |
Specification
| Power Requirements |
| Power Consumption |
195 mA @ 24 VDC (always on) |
| Power Input |
24 VDC nominal, 12 to 36 VDC |
| Analog Input |
| Input Impedance |
200K ohms (min.) |
| Built-in Resistor for Current Input |
102 ohms |
| Resolution |
16 bits |
| Input Range |
0 to 10 V, ±10 V, ±5 V, 0 to 20 mA, 4 to 20 mA |
| Sampling Rate (all channels) |
100 samples/sec |
| Accuracy |
• ±0.1% FSR @ 25°C • ±0.3% FSR @ -30 and 70°C |
| I/O Mode |
Voltage / Current |
| Inputs and Outputs |
| Relay Outputs |
2 channels |
| Analog Inputs |
4 channels |
| Configurable DIOs |
8 channels |
| Relay Output |
| Isolation |
3K VDC or 2K Vrms |
| Initial Insulation Resistance |
1G min. @ 500 VDC |
| Initial Contact Resistance |
30 milli-ohms (max.) |
| Contact Rating |
1 A @ 30 VDC, 1 A @ 240 VAC, 1 A @ 110 VAC |
| Expected Life |
100,000 times (Typical) |
| Inductance Load |
2 A |
| Resistance Load |
5 A |
| Pulse Output |
20 operation times per minutes at rated load |
| Breakdown Voltage |
500 VAC |
| Relay On/Off Time |
10 ms, 5 ms (max.) |
| LAN |
| Protection |
1.5 KV magnetic isolation |
| Ethernet |
1 x 10/100 Mbps, RJ45 |
| Protocols |
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, SNTP |
| Digital Input |
| Isolation |
3K VDC or 2K Vrms |
| Poweroff Counter |
Supports poweroff counter storage function |
| Common Type |
4 points per COM |
| Over-voltage Protection |
36 VDC |
| Digital Filtering Time Interval |
Software selectable |
| Dry Contact |
• On: short to GND • Off: open |
| Wet Contact |
• On: 0 to 3 VDC • Off: 10 to 30 VDC |
| Counter Frequency |
900 Hz, power off storage |
| I/O Mode |
DI or Event Counter |
| Sensor Type |
Wet Contact (NPN or PNP) and Dry Contact |
| Environmental Limits |
| Operating Temperature |
Standard Model: -10 to 55°C (14 to 131°F) Wide Temp. Model: -30 to 70°C (-22 to 158°F) |
| Storage Temperature |
-40 to 85°C (-40 to 185°F) |
| Ambient Relative Humidity |
5 to 95% (non-condensing) |
| Physical Characteristics |
| Weight |
495 g |
| Dimensions |
46.8 x 135 x 105 mm (1.84 x 5.31 x 4.13 in) |
| Standards and Certifications |
| EMI |
FCC Part 15 Subpart B Class A, EN 55022 Class A |
| Safety |
UL 508 (Pending) |
| Shock |
IEC 60068-2-27 |
| Vibration |
IEC 60068-2-6 |
| EMS |
IEC 61000-4, IEC 61000-6 |
| Freefall |
IEC 60068-2-32 |
| Mobile Network |
PTCRB |
| Digital Output |
| Type |
Sink |
| Isolation |
3K VDC or 2K Vrms |
| Pulse Output Frequency |
1 kHz |
| Over-temperature Shutdown |
160°C |
| Over-voltage Protection |
45 VDC |
| Current Rating |
200 mA per channel |
| I/O Mode |
DO or Pulse Output |
| Over-current Protection |
2.6 A (4 channels @ 650 mA) |
| Serial Communication |
| Interface |
1 x RS-232/422/485, software selectable (9-pin D-Sub male, or 5-contact terminal block) |
| Baudrate |
300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps |
| MTBF (mean time between failure) |
| Time |
196,561 hrs |
| Database |
Telcordia (Bellcore) |
| Warranty |
| Warranty Period |
2 years |
| Details |
See www.moxa.com/warranty |
| Cellular |
| Interface |
GSM/GPRS/EDGE |
| GPRS Terminal Device Class |
Class B |
| GPRS Multi-Slot Class |
Class 10 |
| SMS |
Point-to-Point Text/PDU |
| Band Options |
Quad-band GSM/GPRS/EDGE 850/900/1800/1900 MHz |
| SIM Control Voltage |
3 V |
|
|